how to calibrate a pneumatic control valve?
fisher control valve
Answer:
For any pnuematic control valve the operating pressure is from 3 to fully opened at 15 psig. It means a pnuematic control valve opens fully at 15 psi and closes at 3 psig.
To calibrate it,prepare the following, one mercury manometer 0 tp 1000mm,Hg, one air pressure regulator for 20psig supply and air hoses,3 to15 psi output gauge, micrometer screw pressure regulator and air pressure supply. Prepare a Tee with the air supply at the center.Connect one leg to the mercury manometer and the other equalizer leg to the control valve and a tee on top of the valve and an output gauge connected to the tee.. Both the manometer and control valve should receive equal pressure from the pressure regulator. A 15psig pressure is 775 mm mercury . So, set the mercury manometer to an equivalent of 15 psig,775mmHg, and prepare a table of equivalent pressure from 3, 6, 9, 12 and 15psig. The valve should be fifty percent open at 9 psig and 25% open at 6 psig, likewise, it should close at 3 psig and 75% open at 12 psig fully opened at 15 psig. The pressure variation may be done with the micrometer type pressure regulator at the pressure supply.